Fire Extinguishers

ext

The Oregon Fire Code requires all commercial occupancies to provide a minimum of one approved fire extinguisher. Below are the requirements to reference when purchasing an extinguisher for your commercial occupancy.

  • The minimum size required is a 2A:10BC (5 pound) extinguisher
  • The extinguisher is required to be mounted in a conspicuous location where it is readily accessible and immediately available for use
  • The extinguisher must be mounted to higher than 5-feet (60 inches) from the ground and no lower than 4 inches above the ground
  • The maximum travel distance to reach an extinguisher is 75-feet
  • The Oregon Fire Code requires a Class K extinguisher be provided within 30-feet of travel distance from any commercial cooking appliances involving solid fuels, oils, or fats. 

The Oregon Fire Code requires that all fire extinguishers be serviced annually by a certified professional technician. For a list of area contractors who perform service on fire protection systems and extinguishers, please see the link below titled Willamette Valley Service Companies. 

The Lebanon Fire District offers fire extinguisher classes at no charge for district residents. For more information, contact the Deputy Fire Marshal at 541-451-1901 or kfoster@lebanonfire.com